Pair of short flanged braided metal hose assemblies for pump vibration

Home / Tech Reference / Vibration Installation Guide

Metal Hose for Vibration Absorb the shake, not the stress.

Braided metal hose isolates vibration from pumps, compressors, engines and blowers when it is installed the right way round. Here is how to orient, size and anchor it.

90°Hose axis to the vibration
2 hosesOr a dog leg for motion in more than one direction
ShortLive length for small amplitude
AnchorThe pipe side, not the hose

Orientation: across the vibration, never along it

A braided corrugated hose flexes easily sideways and hardly at all along its own axis. The braid locks the hose length, so vibration pushing along the hose axis is fought by the braid and the corrugations instead of being absorbed. Install the hose so its axis is at 90° to the direction of vibration, and the hose bends slightly with each cycle the way it is designed to.

Vibration directionHose orientationResult
Vertical, such as a pump on isolatorsHorizontal hoseHose flexes sideways: correct
Horizontal, across the pipeHose in line with the pipeHose flexes sideways: correct
Along the pipe axisHose in line with the pipeAxial loading: wrong, use a dog leg or turn the hose 90°

Keep the flexing in the plane of any bend in the hose, and keep a short straight section at each fitting so the flexing does not concentrate at the braid collar.

Motion in more than one direction

Engines, compressors and equipment on spring isolators often move in two or three directions at once. A single straight hose can only take the motion that is across its axis. The usual answers:

  • Two hoses at right angles. One hose in each of two planes, joined by an elbow, so every direction of motion is across at least one hose.
  • A dog-leg offset. Two hose legs joined by a 90° elbow, built as one assembly. See dog-leg offset assemblies.
  • A loop. For large thermal movement plus vibration, a U-loop or V-loop takes motion in all three directions.

Live length for vibration

Vibration amplitude is usually small compared with thermal movement, so a pump connector does not need much live length. Longer is not better: a long hose can sag, whip or set up its own resonance. Use the live length tables for pump connectors as a starting point, and check any larger offset or thermal movement with the Live Length Calculator. If the hose also takes thermal growth or misalignment, size it for that movement and treat vibration as continuous flexing in the Flex Service Screening tool.

Anchoring and support

  • Anchor the pipe side. Put a fixed anchor or rigid support on the piping at the far end of the hose from the equipment, so the hose is the only flexible element between the vibrating machine and the fixed pipe.
  • Carry the pipe weight. The hose should not hold up the piping. Support the pipe independently on both sides.
  • Use the hose for vibration only. A pump connector is not a fix for misaligned nozzles. Bringing flanges together by stretching or offsetting the hose uses up its flexibility before it starts working.

Common mistakes

  1. Hose in line with the vibration. The most common failure. The braid and corrugations fatigue quickly.
  2. Twisting at installation. Torsion cuts flex life sharply. Use two wrenches and a floating flange or union where you can.
  3. No anchor on the pipe side. The vibration passes straight through the hose into the piping.
  4. Too much live length. A long hose can resonate and whip. Keep it as short as the movement allows.
  5. Unbraided or helical hose in vibration. Use braided annular hose, which handles cycling best and does not torque under pressure.
Send the motion with your request. Tell us the equipment, the direction and approximate amplitude of the vibration, any thermal or offset movement and the space you have. Hose construction, live length, ratings and dimensions are confirmed by Patriot FTS at quote.

Frequently asked questions

Which way should a metal hose be installed for vibration?
With the hose axis at 90° to the direction of vibration, so the hose flexes sideways. Vibration along the hose axis is resisted by the braid and causes fatigue.
What if the vibration is in more than one direction?
Use two hoses at right angles joined by an elbow, or a dog-leg offset assembly, so every direction of motion is across at least one hose leg.
How long should a pump connector be?
Only as long as needed. Vibration amplitude is small, and a long hose can sag or resonate. Use the pump connector length tables as a starting point.
Can a pump connector correct misaligned flanges?
It should not. Using the hose to take up misalignment uses its flexibility before it starts absorbing vibration and shortens its life.
Where should the anchor go?
On the piping at the end of the hose away from the equipment, so the hose is the only flexible element between the machine and the fixed pipe.